Wednesday, 12 August 2015 09:39 Written by 
Rate this item
(0 votes)

PCT200i

PCT200i

These new CT/PT testers are based on low frequency and variable frequency methods which lead to the great reduction in weight and high knee point test range. With one button click, all test items of the current transformer test set, such as excitation, winding resistance, polarity, phase error, ratio, etc, can be performed automatically.

PCT200i is specially designed for current transformer characteristic test.This CT analyzer can finish the measurement class CT and TYP class CT.The additional functions include ratio and angle differential tests (the measurement points in the GB standard),FS and inductance,steady-state parameters,peak error and transient parameters,etc. 

Features

  • Test CT according to IEC60044-1/6
  • Can test all types of CT, including bushing and GIS type CT
  • One test can get all CT parameters
  • Fast test time for excitation test
  • 10kV knee point test: 50s
  • 1kV knee point test: 15s
  • Ratio check up to 30,000:1
  • Knee point check up to 30,000V
  • Lightweight, Automatic and Compact CT/PT tester with large LCD display, onboard memory and computer interface
  • Principle based on variable frequency method which leads to high knee point test voltage range
  • Testing CT Ratio by voltage method, having fast response time, high precision and reliability
  • Embedded microprocessor digital platform without external PC, easy to operate and reduces test time
  • With one click following test can be performed such as excitation, winding resistance, polarity, phase error, ratio, etc
  • Name Plate Guessing facility
  • Ratio error and phase error list automatically shown when the rated current is 1% to 300%.
  • Inbuilt Demagnetization facility
  • PT test functions are also in-built
  • Test results can be saved to flash disk
  • Optional Excel format report generation
  • Large color LCD display
  • Weight : 14kg

Specifications

 

Parameters PCT200i
 Output Voltage range  0 to 120V
 Output Current range  0 to 5A rms (15A Peak)
Output Power 0.0001 to 500VA rms (1,500VA Peak)
Ratio Test range 30000:1 to 45000:5
Ratio Test Accuracy 0.1%
Max. Knee point voltage 30,000V
Burden test range 0.5 to 200Ω
Burden test accuracy ± 0.1% ± 1mΩ
Winding Resistance test range 0.05 to 200Ω
Winding Resistance test accuracy ± 0.1% ± 1mΩ
Display 8.4 inch, Colour LCD
Operating System Windows
Dimension (W x H x L) 470 x 200 x 245mm
Weight 14Kg
Read 8156 times Last modified on Tuesday, 13 October 2015 08:15