CFL PL2+
The new generation CFL PL2+ Cable Fault Prelocator from SCOPE is the ultimate solution for locating underground cable faults in minimum time. It uses advanced technology for fault distance measurement which helps even an unskilled operator to locate the fault accurately up to 50 km.
CFL PL2+ portable Prelocator is used for identification of fault types in underground cables and the distance of fault. These products are designed to find out various types of faults in the cable such as Open Circuit, Short Circuit, Splice in Cable, High Resistance, Moisture Ingress, etc. Various modes of operation combined with advanced features offer the user the most effective solution for the job
Features
- Compact, Lightweight and Rugged
- User-friendly operation
- Wide measurement range up to 50km
- Highest measurement accuracy up to 0.04%
- A high-speed sampling of 100MHz
- Multiple waveform comparison with Subtraction mode to show waveform differences
- Zoom function for a detailed review of the waveform
- Asynchronous interference & noise suppression
- Adjustable Gain and Balance
- Inbuilt Cable Library for easy setup and testing
- Inbuilt memory to store 100 waveforms
- RS-232 port for communication
- High resolution 5.7” Monochrome LCD display
- Mains, as well as Inbuilt Rechargeable Battery, operated
- Housed in IP67 class moulded case
Specifications
Parameters | CFL PL2+ | |||||||
Modes Of Operations |
TDR: Time Domain Reflectometry / Low Voltage Pulse-echo SIM / MIM / ARC : Secondary Impulse / Arc Reflection/Multiple Impulse |
|||||||
Sampling Rate | 100MHz | |||||||
Measurement Range | Up to 50 Km | |||||||
Measurement Accuracy | 0.04% to 0.4% | |||||||
Resolution | 0.01m | |||||||
Pulse Amplitude (OCV) | 10V | |||||||
Pulse Width | 10nS to 100μS | |||||||
Output Impedance | 25Ω to 600Ω (Default 75Ω) | |||||||
Velocity of Propagation (VoP)/Propagation Factor (PF) Settings | Parameters | PF | V/2 | |||||
From | 1.000 | 50m/μS | ||||||
To | 3.000 | 150m/μS | ||||||
Memory | 100 Waveforms | |||||||
Connectivity | RS-232 | |||||||
Cable Library | >100 Settings | |||||||
Display | 5.7" Monochrome, LCD | |||||||
Battery | Rechargeable Lithium-Ion, Suitable for 8-hour operation | |||||||
Charger Input Supply | 90V to 264V AC, 47 to 63 Hz, Single Phase | |||||||
Environmental | -10°C to +50°C, up to 95% RH (Non-Condensing) | |||||||
Dimension | 270mm x 240mm x 120mm | |||||||
Weight | 2.5 Kg |