XC-2100E
XC 2100E, a Fault Location System based on principle of travelling wave detection is the solution to above problem. It can detect not only permanent fault, but also transient fault within one tower span accuracy (with best accuracy of ±50 meters). It is a kind of Line Monitor for continuous monitoring of transmission lines and gets triggered whenever travelling waves are generated on line due to switching, lightening or fault.
There are various methods employed for fault location detection. However the most suitable is Double End Method in which XC 100E are installed on both ends of the line, and are time synchronised by built-in GPS Module.
The data from both Units is brought to a Master Station where the Master Station Software XCF 2100E is installed. It automatically calculates the distance of fault from each end of line. Each XC 100E is capable of monitoring up-to 8 lines and the Master Station Software is capable of handling large no. of lines in a network.
Features
- TWFL system is free from influence of following factors which aff ect fault location accuracy of impedance based measurement methods like:
- Resistance of line
- Voltage & Current Transformer (CT & PT) errors
- Insufficient accuracy of line parameters due to neglecting of line transposition, distributed capacitance etc.
- Uncertainty of zero sequence impedance due to variation of earth resistance along the line corridor
- Load flow
- TWFL system monitors travelling waves at both ends of transmission lines & provides accurate fault location(fault distance, tower number) for all type of power lines including:
- AC, HVDC and Series Compensated Transmission Lines
- Lines with T branches
- Lines containing cable and overhead line sections
- Measuring fault distance of single phase to ground fault in non-eff ectively earthed Distribution System
- Travelling wave measurement technique used gives fault location within one tower span and with best accuracy of ±50 meters irrespective of line length, line parameters, fault resistance, CVT transients, conductor & tower geometry.
- Such accurate fault location greatly reduces the search time to find out the fault to help quick recovery of the system.
Specifications
Parameter | XC-2100E |
No. of Channels | 3-24 configurable for 1-8 line |
Input Module | AD Module: Direct current input from substation Protection CT |
AI Module with split core CT: Current Input through a split core CT | |
AI Module with external CT: Current Input through an external CT | |
AV Module: Input from substation VT | |
Length of Transient Record | 1 to 20ms Programmable |
Power | 85 to 264V, 50/60 Hz AC or 90 to 260V DC |
Sampling Frequency | 36 MHz, 12 MHz, 8 MHz, 6 MHz, 4.8 MHz, 4 MHz, 3 MHz, 2.4 MHz, 1.5 MHz, 1 MHz & 500 kHz |
Accuracy of Fault Location | Best Accuracy to ±50 meter |
GPS Accuracy | 100ns |
Memory | 8 GB |
Communication port | 2 Ethernet ports, 2 DB9 RS232, USB |
Communication protocol | IEC60870-5-104, IEC 61850 |
Immunity | Conforms to relevant IEC standards |
Operating Temperature | - 10°C - 55°C |
Storage Temperature | -40°C to 85°C |
Physical Dimension | 2U, 19” |