Insulation Resistance Measurement (6)
MD 15KVR
The digital insulation tester model MD-15KVR is Megabras' cutting edge insulation analyzer equipment and it is one of the most complete and sophisticated available in the international market. A powerful software allows for further analysis of tests results, including features such as graphical representation and automatic report generation. Its proven technology provides safe, reliable and accurate measurements of insulation resistances up to 15 TΩ, with 4 pre-selected test voltages, 500 V - 5 kV - 10 kV - 15 kV. Other test voltages may be selected in steps of 25 V, 100 V or 500 V.
A state-of-the-art microprocessor controls the equipment operation and enables the incorporation of advanced features which make measurements easier: auto-range selection, 16,000 readings memory, AC/DC voltmeter, automatic measurement of Absorption Index and Polarization Index, leakage current and capacitance measurement, timer enabling programming of test duration, configurable Pass-Fail test, Step voltage test, real time clock and calendar. Built-in chronometer, indicating elapsed time, in minutes and seconds, since the test started, up to 90 minutes.
Measured values are transmitted through the USB interface and are printed in the built-in printer as a registration of the performed test.The MD-15KVR has a Bluetooth interface that allows remote control of it through a Android device with BlueLogg software. With it you can take the photos of the objects under test and the GPS coordinates of each. It also allows you to record voice comments for each measurement.
Features
- Insulation resistances up to 15 TΩ
- Remote control through an Android app
- Automated tests:
- Absorption index
- Polarization index
- Capacitance
- Leakage Current
- AC/DC voltmeter
- Step Voltage Test
- Real time clock and calendar
- Built-in printer
- 16,000 readings memory
- Software for data management
Specifications
Specification | MD 15kVr | ||
Test voltage |
500 V, 5,000 V, 10,000 V, 15,000 V directly, one button selectable. 500 V to 10 kV in 25 V, 100 V or 500 V steps. DC, negative. |
||
Maximum resistance reading | 15 TΩ @ 10 kV up to 15 kV | ||
DC Voltmeter |
15 V up to 1,000 Vdc. Accuracy: ±(5% of reading + 3 digits). |
||
AC voltmeter |
15 V up to 1000 Vr.m.s. Accuracy: ±(5% of reading + 3 digits) |
||
Overvoltage Category | CAT -III 600V | ||
Capacitance measurement |
50 nF up to 10 µF @ 500 V. 50 nF up to 5 µF @ 1,000 V. 30 nF up to 2 µF @ 2,500 V. 30 nF up to 1 µF @ 5,000 V. 30 nF up to 680 nF @ 10,000 V. 30 nF up to 680 nF @ 15,000 V. Accuracy: ±10% of reading ± 3 digits. |
||
Short circuit current | Max. 2 mA | ||
Test voltage accuracy | ± 3% of nominal test voltages on GΩ | ||
Insulation tester basic accuracy |
± 5% of reading from 1 MΩ to 1 TΩ @ 15 kV. ± 20% of reading from 1 TΩ to 10 TΩ @ 15 kV. (for lower test voltages, the upper limit will be reduced proportionally) ± 20% of reading ± 5 digits from 10 kΩ to 100 kΩ. ± 10% of reading ± 5 digits from 100 kΩ to 1 MΩ. |
||
Advanced features |
Dielectric discharge. Ramp test. Automated Polarization Index calculation. Automated Dielectric Absorption Ratio calculation. Programmable Pass-Fail test. Step Voltage Test. 16,000 Readings memory. Switchable filter to remove external noise interference. |
MD 10KVR
The digital insulation tester model MD-10KVR is Megabras' cutting edge insulation analyzer equipment and it is one of the most complete and sophisticated available in the international market. A powerful software allows for further analysis of tests results, including features such as graphical representation and automatic report generation. Its proven technology provides safe, reliable and accurate measurements of insulation resistances up to 10 TΩ, with 4 pre-selected test voltages, 500 V - 5 kV - 10 kV - 15 kV. Other test voltages may be selected in steps of 25 V, 100 V or 500 V.
A state-of-the-art microprocessor controls the equipment operation and enables the incorporation of advanced features which make measurements easier: auto-range selection, 16,000 readings memory, AC/DC voltmeter, automatic measurement of Absorption Index and Polarization Index, leakage current and capacitance measurement, timer enabling programming of test duration, configurable Pass-Fail test, Step voltage test, real time clock and calendar. Built-in chronometer, indicating elapsed time, in minutes and seconds, since the test started, up to 90 minutes.
Measured values are transmitted through the USB interface and are printed in the built-in printer as a registration of the performed test.The MD-10KVR has a Bluetooth interface that allows remote control of it through a Android device with BlueLogg software. With it you can take the photos of the objects under test and the GPS coordinates of each. It also allows you to record voice comments for each measurement.
Features
- Insulation resistances up to 10 TΩ
- Remote control through an Android app
- Automated tests:
- Absorption index
- Polarization index
- Capacitance
- Leakage Current
- AC/DC voltmeter
- Step Voltage Test
- Real time clock and calendar
- Built-in printer
- 16,000 readings memory
- Software for data management
Specifications
Specification | MD 10KVR | ||
Test voltage |
500 V, 1,000 V, 5,000 V, 10,000 V directly, one button selectable. 500 V to 10 kV in 25 V, 100 V or 500 V steps. DC, negative. |
||
Maximum resistance reading | 10 TΩ @ 5 kV up to 10 kV | ||
DC Voltmeter |
15 V up to 1,000 Vdc. Accuracy: ±(5% of reading + 3 digits). |
||
AC voltmeter |
15 V up to 1000 Vr.m.s. Accuracy: ±(5% of reading + 3 digits) |
||
Overvoltage Category | CAT -III 600V | ||
Capacitance measurement |
50 nF up to 10 µF @ 500 V. 50 nF up to 5 µF @ 1,000 V. 30 nF up to 2 µF @ 2,500 V. 30 nF up to 1 µF @ 5,000 V. 30 nF up to 680 nF @ 10,000 V. Accuracy: ±10% of reading ± 3 digits. |
||
Short circuit current | Max. 2 mA | ||
Test voltage accuracy | ± 3% of nominal test voltages on GΩ | ||
Insulation tester basic accuracy |
± 5% of reading from 1 MΩ to 1 TΩ @ 10 kV. ± 20% of reading from 1 TΩ to 10 TΩ @ 10 kV. (for lower test voltages, the upper limit will be reduced proportionally) ± 20% of reading ± 5 digits from 10 kΩ to 100 kΩ. ± 10% of reading ± 5 digits from 100 kΩ to 1 MΩ. |
||
Advanced features |
Automated Polarization Index calculation. Automated Dielectric Absorption Ratio calculation. Programmable Pass-Fail test. Step Voltage Test. 16,000 Readings memory. Switchable filter to remove external noise interference. |
MD 5KVr
The digital insulation tester model MD5KVR is TENTECH's cutting edge insulation analyzer equipment and it is one of the most complete and sophisticated available in the international market. A software allows for further analysis of tests results, including features such as graphical representation and automatic report generation. Its proven technology provides safe, reliable and accurate measurements of insulation resistances up to 5 TΩ, with 4 preselected test voltages, 500 V -1 kV - 2,5 kV - 5 kV. Other test voltages, from 50 V to 5 kV, can be selected in 25 V or 500 V steps.
A state-of-the-art microprocessor controls the equipment operation and enables the incorporation of advanced features which make measurements easier: auto-range selection, AC/DC voltmeter, automatic measurement of absorption index, polarization index, leakage current and capacitance, timer enabling programming of test duration, configurable pass-fail test, dielectric discharge, ramp test, step voltage test, built-in printer, real time clock and calendar.
Measured values are transmitted through the USB interface and are printed in the built-in printer as a registration of the performed test. Furthermore, the measured values are stored in a non-volatile internal memory. Up to 16,000 measured values may be stored to be transferred afterward to a computer running the T-Logger program. This software allows a further analysis of the test results, including a graphical representation and automatic report generation. The real time clock and calendar, and the sequential test number, facilitates the identification of each test, and the organization of a predictive maintenance system by trend analysis.
The MD5KVR is powered by a rechargeable LFP battery. The cabinet is strong and lightweight, easy to carry, impact-resistant and suitable to be used under severe weather conditions. Thus the megohmmeter supplies very reliable and accurate measurements both in laboratory and out in the field.
Features
- Microprocessor-controlled
- Insulation resistances up to 5 TΩ
- Auto-range
- Automated tests: Absorption index, Polarization index, Capacitance, Leakage current and AC/DC voltmeter
- IP65 protection
- Switchable filter to remove external noise interference
- Real time clock and calendar
- Built-in printer, internal memory for up to 16,000 measured values
- Software for data management
Specifications
Specification | MD 5KVR | ||
Test voltage |
500 V - 1 kV - 2,5 kV - 5k V directly, one button selectable. 50 V to 5 kV in 25 V or 500 V steps. DC, negative. |
||
Maximum resistance reading |
5 TΩ @ 5 kV 250GΩ @250V |
||
DC Voltmeter |
15 V up to 1,000 Vdc. Accuracy: ±(5% of reading + 3 digits). |
||
AC voltmeter |
15 V up to 1000 V r.m.s. Accuracy: ±(5% of reading + 3 digits) |
||
Overvoltage Category | CAT -III 600V | ||
Capacitance measurement |
50 nF up to 10 µF @ 500 V. 50 nF up to 5 µF @ 1,000 V. 30 nF up to 2 µF @ 2,500 V. 30 nF up to 1 µF @ 5,000 V. Accuracy: ±10% of reading ± 3 digits. |
||
Short circuit current | Max. 3 mA | ||
Test voltage accuracy | ± 3% of nominal test voltages on 10 GΩ | ||
Insulation tester basic accuracy |
± 5% of reading from 1 MΩ to 1 TΩ @ 5 kV. ± 20% of reading from 1 TΩ to 5 TΩ @ 5 kV. (for lower test voltages, the upper limit will be reduced proportionally). ± 20% of reading ± 5 digits 10 from kΩ to 100 kΩ. ± 10% of reading ± 5 digits 100 from kΩ to 1 MΩ |
||
Advanced features |
Ramp test. Dielectric discharge. Step voltage test. Automated polarization index calculation. Automated dielectric absorption ratio calculation. Programmable pass-fail test. 16,000 readings memory. Switchable filter to remove external noise interference. |
MD 5060x
The Megabras MD-5060x is a smart, microprocessor-controlled, 5kV insulation tester and analyzer. Besides the conventional measurement of insulation resistances up to 5 TW, its advanced features allow to automatically measure both the Polarization Index and Dielectric Absorption Index, thus significantly simplifying testing of transformers.
This insulation tester is a portable, battery-powered equipment. Test voltage may be chosen from 500V to 5 kV in 100 dddV increments. Due to its measurement principle (actual voltage and current readings) the accuracy of resistance measurement is not affected by any test voltage error. Nevertheless, the High-Voltage generator is electronically stabilized with a better than 2% accuracy in open-circuit condition and for any normal operation battery voltage.
The MD-5060x is powered using a rechargeable battery and has an automatic charger that may be connected to 100 - 240V mains supply. The cabinet is strong and lightweight, easy to carry, impact-resistant and suitable to be used under severe weather conditions. Thus the megohmmeter supplies very reliable and accurate measurements both in laboratory and out in the field.
Features
- Insulation resistance
- Auto-range
- Guard terminal
- Automated tests:
- Absorption index
- Polarization index
- Real time clock
- 4000 Readings memory
- USB Interface
- Programable pass-fail
- Built-in printer
- Rechargeable battery
Specifications
Specifications | |
Test Voltages |
500 V, 1,000 V, 2,500 V, 5,000 V directly, one button selectable 500 V to 5 kV in 100 V increments. DC, negative. |
Maximum resistance reading | 5 TΩ @ 5 kV. |
Short circuit current | 1.5 ± 0.5 mA. |
Megohmmeter basic accuracy | ± 3% of nominal test voltages on 10 GΩ. |
Advanced features |
Automated Polarization Index calculation. Automated Dielectric Absorption Ratio calculation Programmable Pass-Fail test. Step Voltage Test. |
Built-in printer | Prints elapsed time, actual voltage and resistance measured each 15 seconds. |
MI20KVe
The MI-20KVe High-Voltage insulation tester is a truly portable device that allows the measurement of insulation resistances using test voltages up to 20 kV.
It employs a state-of-the-art technology for the safe measurements of insulation resistances up to 4,000,000 MΩ with four test voltages: 5 kV - 10 kV - 15 kV and 20 kV.
Analogue indicator, having a broad scale.
Due to its reduced size and weight, its power autonomy and mechanical strength, this insulation tester is suitable for working out in the field, under severe weather conditions. It is powered with a rechargeable battery, with a charger for 110 V/220 V. In order to protect the equipment, the cabinet is water and dust resistant. Protection grade is IP54, and the insulation tester is supplied with a complete kit of high voltage test leads.
Features
- Insulation test up to: 4 TΩ
- 4 Test voltages: 5 kV - 10 kV - 15 kV - 20 kV
- Guard terminal
- Rechargeable battery
- Multiple scales for precision improvement
- Portable, accurate & rugged
- IP-54 Protection
Specifications
Specifications | |||
Test voltages | 5 kV - 10 kV - 15 kV - 20 kV. | ||
Maximum resistance reading |
1 TΩ @ 5 kV. 2 TΩ @ 10 kV. 3 TΩ @ 15 kV. 4 TΩ @ 20 kV. |
||
Short circuit current | 500 µA. | ||
Test voltage accuracy | ± 2% of nominal test voltages on R ≥ 10 GΩ. | ||
Internal current limiting resistance |
10 MΩ @ 5 kV. 20 MΩ @ 10 kV. 30 MΩ @ 15 kV. 40 MΩ @ 20 kV. |
||
Insulation tester Accuracy | Class 2 (±2 % of full scale deflection). | ||
Analogue indicator | Up to 98 mm scale length, taut band, with mirror |
MI15KVe
The MI-15KVe High-Voltage insulation tester is a truly portable device that allows the measurement of insulation resistances using test voltages up to 15kV.
It employs a state-of-the-art technology for the safe measurements of insulation resistances up to 3,000,000 MW with four test voltages: 1 kV - 5 kV - 10 kV and 15 kV.
Readings are performed through an easy-toread analogue indicator, having a broad scale.
Due to its reduced size and weight, its power autonomy and mechanical strength, this insulation tester is suitable for working out in the field, under severe weather conditions. It is powered with a rechargeable battery, with a charger for 110 V/220 V. In order to protect the equipment, the cabinet is water and dust resistant. Protection grade is IP54, and the insulation tester is supplied with a complete kit of high voltage test leads.
Features
- Insulation test up to: 3 TΩ
- 4 Test voltages: 1 kV - 5 kV - 10 kV - 15 kV
- Guard terminal
- Rechargeable battery
- Multiple scales for precision improvement
- IP-54 Protection
Specifications
Specifications | |
Test voltages | 1 kV - 5 kV - 10 kV - 15 kV. |
Maximum resistance reading |
200 GΩ @ 1 kV. 1 TΩ @ 5 kV. 2 TΩ @ 10 kV. 3 TΩ @ 15 kV |
Short circuit current | 1 mA. |
Test voltage accuracy | ± 2% of nominal test voltages on R ≥ 10 GΩ. |
Internal current limiting resistance |
1 MΩ @ 1 kV. 5 MΩ @ 5 kV. 10 MΩ @ 10 kV. 15 MΩ @ 15 kV. |
Insulation tester Accuracy | Class 2 (±2 % of full scale deflection). |
Analogue indicator | Up to 98 mm scale length, taut band, with mirror. |