SCOPE has partnered with Vizimax Inc, Canada as an exclusive distributor for Vizimax PMU (Phasor Measurement Unit) to the Indian Electricity Grids.

 

Major Features 

  • Current and voltage Phasors, frequency and ROCOF measurements exceeding C37.118 requirements for both M and P classes. Adjustable reporting rates: Up to 200/240 frames per second for 50/60 Hz.
  • Broad variety of time synchronization methods from external sources and precisions clocks, either standalone or networked.
  • Optional built-in GPS Receiver allowing for precision time synchronization even in the absence of external sources or clocks. 
  • Precision time synchronization server: synchronize other devices, IEDs, controllers when fitted with the built-in GPS Receiver or when synchronized via PTP 1588. 
  • IEC 61850 GOOSE Messaging Publisher. IEC 61850 GOOSE Messaging Subscriber.
  • Vizimax PMU is an IEEE certified product.
  • IP based web monitoring system which will give a complete information regarding the phasor measurements to monitor the locally.

For more information or detailed technical seminar/webinar, please contact us at This email address is being protected from spambots. You need JavaScript enabled to view it.

 

 

 

SCOPE offers Wide Area Monitoring System (WAMS) Simulation System for Research Institutes and University laboratories for student engagement and research purpose.

SCOPE entered into business of Protection division through control & relay panel. Through its state of art factory which can handle around 200 panels at a time. With the intention to provide correct solution to customer at a correct price, SCOPE entered into this business in 2009.

Control & Relay Panels

We at SCOPE T&M Pvt Ltd have developed our expertise to meet customer expectation in the area of Design, Engineering, Manufacturing & testing 33KV to 765KV Control & Relay Panels. With our ‘State of the Art’ Factory set up at Pune. We can handle multiple projects with the production capacity up to 200 Panel per month. Know More


Substation Automation System

Digitisation of Electrical Substations is the need of the hour as electrical grid networks keep expanding to accommodate new energy sources and increased demand from consumers. Automation of Electrical Substations provides Grid Operators with advanced capabilities such as intelligent network-level load flow calculations, forecasting and remote controlling to ensure a reliable and efficient system. Know More


Controlled Switching Device

Our Experience in understanding the DUT(Reactor or Transformer Breakers) through our T&M Vertical has helped us to bring the Intelligent system to operate the CB on ‘ZERO Crossing’ with the ‘point on Wave Controller’ technology in association with our valuable Collaboration. More than 250+ devices are already in operation in Indian Power Sysytem. Know More


RTU Automation Solution

Apart from substation automation we have solution for SCADA/OMS/DMS/EMS required for state load dispatch centres (SLDC’s) and distribution management system. We have excellent RTU based automation system which is extremely cost effective solution for the conventional s/s to convert them to fully automated substation and make them compatible to smart grid. Know More

Circuit Breaker(CB)are designed to switch On & Off the circuit. Under a fault condition; No sooner it receives the command to Open, It opens the circuit but while doing so the CB goes through tremendous stresses and contact are opened to Arc. All this can be reduced using a Controlled Switching. SCOPE in association with Vizimax, Canada offers a Controlled Switching Device (CSD) for MV/HV/ EHV/UHV Circuit Breakers, SynchroTeq series, is the one and only “Manufacturer Agnostic” solution, applicable to either brand new or existing equipment.

This Point on wave operates with intention to have minimum stress on CB while opening or closing keeping the primary function of the CB to switch the circuit in minimal time and without affecting the Grid.

When SynchroTeq Plus receives a CLOSE command, a time delay is initiated, awaiting the first zero-crossing of the phase A voltage for synchronization of the C/B mechanical operation. Should no zero-crossing be detected within the pre-set time delay, controlled switching is aborted and a three-phase random CLOSE is executed if allowed. Should a zero-crossing occur within the pre-set delay and providing no failures are detected, the SynchroTeq Plus sends controlled CLOSE commands to each phase.

The computed time delays are measured from the reference zero-crossing and the time is adjusted to account for environmental factors, measurement sand variations in the C/B characteristics of each phase.



Best Switching strategy for Closing

Load Type R Y B
Capacitor Bank Yg 90° 210° 150°
Capacitor Bank Y and D 30° 120° 30°
Shunt reactor Yg 90° 210° 150°
Shunt reactor Y and D 60° 60° 150°
Transformer Yg- Yg 90° 210° 150°
Transformer Yg- D 90° n*90° n*90°
Line 120° 150°

Best Switching strategy for Opening (Current 0)

Load Type R Y B
Capacitor Bank Yg 90° 210° 150°
Capacitor Bank Y and D 90° 180° 180°
Shunt reactor Yg 90° 210° 150°
Shunt reactor Y and D 90° 180° 180°
Transformer Yg- Yg 90° 210° 150°
Transformer Yg- D 90° 210° n*90°
Line 90° 210° 150°

Applications

  • Capacitor Banks
  • Shunt Inductors
  • Power Transformer

Advantage of using Controlled Switching Device

  • Can be used on any technology of circuit breaker
  • Can manage the energization of power transformers based on the residual flux
  • Advanced C/B timing compensation
  • Fast response time
  • Huge event/waveform memory capacity (2000 Events)
  • Waveforms recordings are COMTRADE compatible
  • Simple and secured web interface
  • Remote support
  • Compatible with IEC 61850, DNP3.0 and MODBUS

The SynchroTeq unit improves the operating conditions of the circuit breaker:

  • It reduces the possibilities of re-strike and re-ignition
  • It reduces the inrush current and optimize the arcing time, and therefore reduce the contact wear on the circuit breaker

Nothing is worse than random closing: therefore, SynchroTeq improves the situation!
The SynchroTeq unit is 100 times more accurate and repeatable than a typical circuit breaker:

  • The SynchroTeq control timing is done using a 10 microsecond resolution
  • The SynchroTeq+ alarm detection and feedback measurement is evaluated using a 100 microsecond resolution.

Isn’t a digital electronic system more accurate and repeatable than a mechanical system such as a circuit breaker?

The SynchroTeq unit records the event and waveforms during the opening and closing operations, therefore it is used as a circuit breaker diagnostic tool:

  • If something goes wrong with the circuit breaker, alarms are generated
  • SynchroTeq records all the alarms an operation, including the waveforms data of the CB operation

 

To download the literature click here